intelligent_platforms_proficy_hmi\/scada_cimplicity

Vendor: ge

Actively Exploited 0 CISA KEV List
PoC / Exploits 1 Code Available
Total RCEs 0 Remote Access
Total CVEs 46 Total Indexed
Avg. EPSS 10.40% Exploit Prob.
Latest CVE CVE-2017-12732 Oct 05

Security Vulnerability Index

Page 1 / 5
6.8 CVSS

A Stack-based Buffer Overflow issue was discovered in GE CIMPLICITY Versions 9.0 and prior. A function reads a packet to indicate the next packet length. The next packet length is not verified, allowing a buffer overwrite that could lead to an arbitrary remote code execution.

EPSS: 0.75%
6.6 CVSS

The (1) CimView and (2) CimEdit components in GE Proficy HMI/SCADA-CIMPLICITY 8.2 and earlier allow remote attackers to gain privileges via a crafted CIMPLICITY screen (aka .CIM) file.

EPSS: 0.65%
6.8 CVSS

The CIMPLICITY Web-based access component, CimWebServer, does not check the location of shell files being loaded into the system. By modifying the source location, an attacker could send shell code to the CimWebServer which would deploy the nefarious files as part of any SCADA project. This could allow the attacker to execute arbitrary code.

EPSS: 2.72%
7.5 CVSS
CVE-2014-0750
Exploit Found

Directory traversal vulnerability in gefebt.exe in the WebView CimWeb components in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY through 8.2 SIM 24, and Proficy Process Systems with CIMPLICITY, allows remote attackers to execute arbitrary code via a crafted HTTP request, aka ZDI-CAN-1622.

EPSS: 70.22%
4.7 CVSS

The (1) Catapult DNP3 I/O driver before 7.2.0.60 and the (2) GE Intelligent Platforms Proficy DNP3 I/O driver before 7.20k, as used in DNPDrv.exe (aka the DNP master station server) in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY and iFIX, allow physically proximate attackers to cause a denial of service (infinite loop) via crafted input over a serial line.

EPSS: 0.76%
7.1 CVSS

The (1) Catapult DNP3 I/O driver before 7.2.0.60 and the (2) GE Intelligent Platforms Proficy DNP3 I/O driver before 7.20k, as used in DNPDrv.exe (aka the DNP master station server) in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY and iFIX, allow remote attackers to cause a denial of service (infinite loop) via a crafted DNP3 TCP packet.

EPSS: 1.85%
9.3 CVSS

Multiple buffer overflows in CimWebServer.exe in the WebView component in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY before 8.0 SIM 27, 8.1 before SIM 25, and 8.2 before SIM 19, and Proficy Process Systems with CIMPLICITY, allow remote attackers to execute arbitrary code via crafted data in packets to TCP port 10212, aka ZDI-CAN-1621 and ZDI-CAN-1624.

EPSS: 3.77%
9.3 CVSS

CimWebServer in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY 4.01 through 8.0, and Proficy Process Systems with CIMPLICITY, allows remote attackers to execute arbitrary commands or cause a denial of service (daemon crash) via a crafted packet.

EPSS: 3.06%
4.3 CVSS

Directory traversal vulnerability in substitute.bcl in the WebView CimWeb subsystem in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY 4.01 through 8.0, and Proficy Process Systems with CIMPLICITY, allows remote attackers to read arbitrary files via a crafted packet.

EPSS: 19.11%
4.3 CVSS

Integer overflow in CimWebServer.exe in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY 4.01 through 8.0, and Proficy Process Systems with CIMPLICITY, allows remote attackers to cause a denial of service (daemon crash) via a malformed HTTP request.

EPSS: 1.15%